magazinelogo

Journal of Electrical Power & Energy Systems

ISSN Online: 2576-053X Downloads: 29095 Total View: 339733
Frequency: semi-annually ISSN Print: 2576-0521 CODEN: JEPEEG
Email: jepes@hillpublisher.com

Volumes & Issues

Current Issue

Article Open Access http://dx.doi.org/10.26855/jepes.2021.11.001

A New Implementation of PMU Based on Streamed Values of IEC 61850 Process-Bus

Ahmed Abdolkhalig*, Ashraf Mohamed, Fatihe Abusief

Department of Electrical Engineering, The University of Tobruk, 4004, Tobruk, Butnan, Libya.

*Corresponding author: Ahmed Abdolkhalig

Published: November 17,2021

Abstract

This paper assessing the performance of a simulated PMU fed by streamed measured values as defined in IEC 61850. The PMU is designed and implemented based on the so-called Unscented Kalman Filter algorithm and proposed as a centralized computation tool. The communications among PMUs and central control room is accomplished based on Ethernet network communications. Although that Ethernet-based communications can be appropriate and reliable for many power applications, it is recommended to assess the impacts of its communication network errors such as network bandwidth and clock errors and how their influence on the estimated phasor. This proposed implementation can help power utilities to track any dynamic change and improve the state estimation of the system. MATLAB®/Simulink® is used in conjunction with true-time software that is developed by ABB to mimic the process-bus communication of IEC 61850 in this work. Representative results in assessing the impacts of the errors on PMU’s performance are presented in the paper.

References

[1] Abur, A. and A. G. Exposito. (2004). Power system state estimation: theory and implementation. 2004: CRC press.

[2] Zivanovic, R. and C. Cairns. (1996). Implementation of PMU technology in state estimation: an overview. In Proceedings of IEEE. AFRICON'96. 1996. IEEE.

[3] Rice, M. J. and G. T. Heydt. (2006). Power systems state estimation accuracy enhancement through the use of PMU measurements. In Proc. 2006 Transmission and Distribution Conference and Exhibition. 2006.

[4] Mackiewicz, R. E. (2006). Overview of IEC 61850 and Benefits. In 2006 IEEE Power Engineering Society General Meeting. 2006. IEEE.

[5] Apostolov, A. (2010). IEC 61850 9-2 process bus applications and benefits. In 10th IET International Conference on Developments in Power System Protection (DPSP 2010). Managing the Change. 2010. IET.

[6] Korba, P., M. Larsson, and C. Rehtanz. (2003). Detection of oscillations in power systems using Kalman filtering techniques. in Proceedings of 2003 IEEE Conference on Control Applications, 2003. CCA 2003. 2003. IEEE.

[7] Wood, H., N. Johnson, and M. Sachdev. (1985). Kalman filtering applied to power system measurements relaying. IEEE Transactions on Power Apparatus and Systems, 1985(12): pp. 3565-3573.

[8] Köse, N., Ö. Salor, and K. Leblebicioglu. (2011). Kalman filtering based approach for light flicker evaluation of power systems. IET generation, transmission & distribution, 2011, 5(1): pp. 57-69.

[9] Perez, E. and J. Barros. (2008). An extended Kalman filtering approach for detection and analysis of voltage dips in power systems. Electric Power Systems Research, 2008, 78(4): pp. 618-625.

[10] Anagnostou, G. and B. C. Pal. (2017). Derivative-free Kalman filtering based approaches to dynamic state estimation for power systems with unknown inputs. IEEE Transactions on Power Systems, 2017, 33(1): pp. 116-130.

[11] Wiltshire, R. A., G. Ledwich, and P. O'Shea. (2007). A Kalman filtering approach to rapidly detecting modal changes in power systems. IEEE Transactions on Power Systems, 2007, 22(4): pp. 1698-1706.

[12] Eidson, J. C., M. Fischer, and J. White. (2002). IEEE-1588™ Standard for a precision clock synchronization protocol for net-worked measurement and control systems. In Proceedings of the 34th Annual Precise Time and Time Interval Systems and Applications Meeting. 2002.

[13] Giorgi, G. and C. Narduzzi. (2011). Performance analysis of Kalman-filter-based clock synchronization in IEEE 1588 networks. IEEE transactions on instrumentation and measurement, 2011, 60(8): pp. 2902-2909.

[14] Martin, K., et al. (2008). Exploring the IEEE standard C37. 118–2005 synchrophasors for power systems. IEEE transactions on power delivery, 2008, 23(4): pp. 1805-1811.

How to cite this paper

A New Implementation of PMU Based on Streamed Values of IEC 61850 Process-Bus

How to cite this paper: Ahmed Abdolkhalig, Ashraf Mohamed, Fatihe Abusief. (2021) A New Implementation of PMU Based on Streamed Values of IEC 61850 Process-Bus. Journal of Electrical Power & Energy Systems5(1), 92-100.

DOI: http://dx.doi.org/10.26855/jepes.2021.11.001